Softstart UK Installation
5. Installation
5.1. Physical Installation
1
4
3
2
2
1
/
L
1
5
/
L
3
3
/
L
2
2/
T
1 6
/
T
3
4/
T
2
1
/
L
1
5
/ L
33
/
L2
2
/
T
1
6
/
T
3
4
/
T
2
B
1
/
L
1
5
/
L
3
3
/
L
2
2
/
T
1
6
/
T
3
4
/
T
2
1/ L 1 5/L33 /L 2
LV-DS-0023B ~ LV-DS-0220B: Allow 100 mm (3.94
inches) between soft starters.
LV-DS-0255B ~ LV-DS-1000B: Allow 200 mm (7.88
inches) between soft starters.
LV-DS-0255C: Allow 100 mm (3.94 inches)
between soft starters.
LV-DS-0360C ~ LV-DS-1600C: Allow 200 mm (7.88
inches) between soft starters.
LV-DS-0023B ~ LV-DS-0220B: Allow 50 mm (1.97
inches) between the soft starter and solid surfaces.
LV-DS-0255B ~ LV-DS-1000B: Allow 200 mm (7.88
inches) between the soft starter and solid surfaces.
LV-DS-0255C: Allow 100 mm (3.94 inches)
between the soft starter and solid surfaces.
LV-DS-0360C ~ LV-DS-1600C: Allow 200 mm (7.88
inches) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no
clearance (that is, if mounted without
The soft starter may be mounted on its side. Derate
the soft starter's rated current by 15%.
5.2. Control Terminals
Control terminations use 2.5mm
2
plug-in terminal blocks. Unplug each block, complete the wiring, then reinsert
the block.
131421 22 24 33 34
40
41 5
3 54
55 56
57 5
8 64
65A4 A5A6
5 4 3
2 1
9 8
7 6
A4 A5 A6
40 4
1 5 3 5
4 5 5
56 5
7 5 8
64 65
13 14 21 22 2 4 3 3
34
13 14 21
22
24 33 34
40 4
1 53 5
4 55
56 5
7 58 64 6
5
A4 A
5 A6
5 4
3 2 1
9 8 7
6
5 4 3 2 1
9 8 7 6
1
2
3
4
1
2
3
4
DB9 connector for remote control panel
NOTE
If you are not using a thermistor, do not short terminals 64, 65.
NOTE
The DB9 connector on the soft starter should only be used to connect to a remote control panel.
Connecting other equipment to this port can damage the soft starter or the equipment.
710-15797-00A – LV-DS User Manual 11/64